//Exa 10.9 clc; clear; close; //Given Data : format('v',7); Pa=500;//in KW cosfi_1=0.7071;//powerfactor tanfi_1=tand(acosd(cosfi_1));//unitless Pr1=Pa*tanfi_1;//in KVAR Pm=100;//in KW P=Pa+Pm;//in KW cosfi_2=0.95;//unitless tanfi_2=tand(acosd(cosfi_2));//unitless Pr=P*tanfi_2;//in KVAR Prm=Pr-Pr1;//in KVAR Pam=sqrt(Pm^2+Prm^2) PFsynMotor=Pm/Pam;//leading PF disp(PFsynMotor,"P.F. of synchronous motor(leading) :");