//Exa 10.8 clc; clear; close; //Given Data : format('v',7); f=50;//in Hz V=400;//in volts MotorOut=20;//in HP(Motor output) MotorOut=MotorOut*735.5;//in Watts(Induction Motor output) CorrectPF=0.85;//in fraction MotorIn=MotorOut/(CorrectPF*1000);//in KW cosfi_1=0.7071;//powerfactor tanfi_1=tand(acosd(cosfi_1));//unitless Pr1=MotorIn*tanfi_1;//in KVAR cosfi_2=0.85;//unitless tanfi_2=tand(acosd(cosfi_2));//unitless Pr2=Pr1*tanfi_2;//in KVAR Prc=Pr1-Pr2;//in KVAR Prc_ph=Prc/3;//in KVAR C=Prc_ph*10^3/(2*%pi*f*V^2) disp(C*10^6,"Rating of each capacitor per phase(in uF)");