//Exa 10.1 clc; clear; close; //Given Data : format('v',7); Load=500;//in KW cosfi_1=0.75;//powerfactor x=40;//in Rs/year/KVA x1=60;//cost of PF improvement equipment in Rs./KVAR i=12;//in % per annum y=x1*i/100;//in Rs. cosfi_2=0.98;//unitless KVA1=Load/cosfi_1;//in KVA(at 0.75 pf) KVA2=Load/cosfi_2;//in KVA(at 0.98 pf) AnnualSaving=x*(KVA1-KVA2);//in Rs. fi_1=acosd(cosfi_1);//in degree tanfi_1=tand(fi_1);//unitless Pr1=Load*tanfi_1;//in KVAR fi_2=acosd(cosfi_2);//in degree tanfi_2=tand(fi_2);//unitless Pr2=Load*tanfi_2;//in KVAR Rating=Pr1-Pr2;//in KVAR AnnualExpenditure=y*Rating;//in Rs. NetSaving=AnnualSaving-AnnualExpenditure;//in Rs./year disp(NetSaving,"Net saving per year(in Rs.) :");