//Chapter-7, Illustration 1, Page 345 //Title: Air Conditioning //============================================================================= clc clear //INPUT DATA DBTo=10;//Out door Dry bulb temperature in oC WBTo=8;//Out door Wet bulb temperature in oC DBTi=20;//In door Dry bulb temperature in oC RH=0.6;//Re-Heat factor a=0.3;//amount of air circulated in (m^3)/min/person S=50;//Seating capacity of office BPF=0.32;//ByPass factor ha=25;//Enthalpy at point a from Psychrometric chart shown in Page 346 in kJ/kg hb=42.5;//Enthalpy at point b from Psychrometric chart shown in Page 346 in kJ/kg hc=42.5;//Enthalpy at point c from Psychrometric chart shown in Page 346 in kJ/kg Wa=0.006;//Specific humidity at point a from Psychrometric chart shown in Page 346 in kg/kg dry air Wc=0.009;//Specific humidity at point c from Psychrometric chart shown in Page 346 in kg/kg dry air Tb=27;//Temperature at point b in oC na=0.81;//Specific Volume from Psychrometric chart shown in page 346 in (m^3)/kg //CALCULATIONS ma=(a*S)/(na*60);//mass of air circulated per second in kg/s Hc=ma*(hb-ha);//Heating capacity of coil in kW Ts=(Tb-(BPF*DBTo))/(1-BPF);//Heating coil surface temperature in oC C=(ma*3600)*(Wc-Wa);//Capacity of humidifier in kg/hr //OUTPUT mprintf('Heating capacity of coil is %3.2f kW \n Surface temperature of coil is %3.0f oC \n Capacity of humidifier is %3.2f kg/hr',Hc,Ts,C)