//Chapter-6, Illustration 5, Page 311 //Title: Refrigeration cycles //============================================================================= clc clear //INPUT DATA T2=40;//Temperature at point 2 in oC T1=-10;//Temperature at point 1 in oC h2=367.155;//Enthalpy at point 2 from refrigerant-12 tables in kJ/kg s2=1.54057;//Entropy at point 2 from refrigerant-12 tables in kJ/kg-K s1=1.54057;//Entropy at point 1 from refrigerant-12 tables in kJ/kg-K sg=1.56004;//Entropy from refrigerant-12 tables in kJ/kg-K sf=0.96601;//Entropy from refrigerant-12 tables in kJ/kg-K hf=190.822;//Enthalpy from refrigerant-12 tables in kJ/kg-K hfg=156.319;//Enthalpy from refrigerant-12 tables in kJ/kg-K h3=238.533;//Enthalpy at point 3 from refrigerant-12 tables in kJ/kg-K h4=h3;//Enthalpy at point 4 from refrigerant-12 tables in kJ/kg-K //CALCULATIONS x1=(s1-sf)/(sg-sf);//Quality factor h1=hf+(x1*hfg);//Enthalpy at point 1 from refrigerant-12 tables in kJ/kg COP=(h1-h4)/(h2-h1);//Co-efficient of performance //OUTPUT mprintf('COP of the system is %3.2f',COP) //==============================END OF PROGRAM=================================