//Chapter-2, Example 2.10, Page 2.17 //============================================================================= clc clear //INPUT DATA Io=12;//Primary no load current in A cosqo=0.25;//No load power factor I2=220;//Secondary load current in A cosq2=0.8;//Secondary power factor K=(1/5);//Turn ratio //CALCULATIONS qo=acosd(cosqo);//phase angle in degree q2=acosd(cosq2);//Phase angle in degree Ioc=complex((Io*cosqo),(Io*sind(qo)));//Io value in complex form I2i=complex((K*I2*cosq2),(K*I2*sind(q2)));//I2i value in complex form I1=(Ioc+I2i);//Primary current in A X=sqrt((real(I1))^2+(imag(I1))^2);//Primary current in A Y=cosd(atand(imag(I1)/real(I1)));//Power factor //OUTPUT mprintf('Primary current is %3.1f A and Primary power factor is %3.2f',X,Y) //=================================END OF PROGRAM==============================