Ybus - 22.888889i 5.952381i 0 0 7.9365079i 5.952381i - 13.888889i 7.9365079i 0 0 0 7.9365079i - 23.174603i 2.9761905i 4.7619048i 0 0 2.9761905i - 6.9444444i 3.968254i 7.9365079i 0 4.7619048i 3.968254i - 16.666667i Zbus 0.0792966i 0.0557999i 0.0381774i 0.0511283i 0.0608415i 0.0557999i 0.1338419i 0.0663734i 0.0630432i 0.0605455i 0.0381774i 0.0663734i 0.0875205i 0.0719793i 0.0603235i 0.0511283i 0.0630432i 0.0719793i 0.2320893i 0.1001717i 0.0608415i 0.0605455i 0.0603235i 0.1001717i 0.1300578i The subtransient current in a three-phase fault on bus 4 in per unit is - 4.3086871i Voltages at bus 3 and 5 repectively in per unit 0.5683915 0.6898635 Currents to fault from bus 3 in per unit - 2.0531653i Currents to fault from bus 5 in per unit - 2.2555218i Total current to fault in per unit - 4.3086871i