//Chapter-12, Example 12.10, Page 517 //============================================================================= clc clear //INPUT DATA Ti=360;//Inlet temperature of hot fluid in degree C taken from Example no. 12.4 on page no. 510 To=300;//Outlet temperature of hot fluid in degree C taken from Example no. 12.4 on page no. 510 ti=30;//Inlet temperature of cold fluid in degree C taken from Example no. 12.4 on page no. 510 to=200;//Outlet temperature of cold fluid in degree C taken from Example no. 12.4 on page no. 510 U=800;//Overall heat transfer coefficient in W/m^2.K taken from Example no. 12.4 on page no. 510 Q=150000;//Calculated heat transfer rate in W from Example no. 12.4 on page no. 510 Tlm=210.22//Calculated LMTD for counterflow arrangement in degree C taken from Example no. 12.4 on page no. 511 //CALCULATIONS P=((to-ti)/(Ti-ti));//P value for calculation of correction factor R=((Ti-To)/(to-ti));//R value for calculation of correction factor F=0.98;//Correction Factor value taken from Fig.12.11 on page no.515 A=(Q/(U*F*Tlm));//Required surface area in a cross flow heat exchanger in m^2 //OUTPUT mprintf('The required surface area in a cross flow heat exchanger is %3.2f m^2',A) //=================================END OF PROGRAM==============================