From b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b Mon Sep 17 00:00:00 2001 From: priyanka Date: Wed, 24 Jun 2015 15:03:17 +0530 Subject: initial commit / add all books --- 83/CH9/EX9.9/result_example_9_9.txt | 24 ++++++++++++++++++++++++ 1 file changed, 24 insertions(+) create mode 100755 83/CH9/EX9.9/result_example_9_9.txt (limited to '83/CH9/EX9.9/result_example_9_9.txt') diff --git a/83/CH9/EX9.9/result_example_9_9.txt b/83/CH9/EX9.9/result_example_9_9.txt new file mode 100755 index 000000000..b05193775 --- /dev/null +++ b/83/CH9/EX9.9/result_example_9_9.txt @@ -0,0 +1,24 @@ + + + The Thevenin passive network for this system is drawn in Example_9_8 (or fig 9.28 in the textbook) + + Using the Zbus matrix from the results of example_9_8,we can calculate post fault currents and voltages + Zbus = + + 0.1397059i 0.1102941i 0.125i + 0.1102941i 0.1397059i 0.125i + 0.125i 0.125i 0.175i + +If=-j5.71 pu + +V1f=0.286 +V2f=0.286 + +I12f=0 +I13f=-j2.86 +I23f=-j2.86 + +Ig1f=-j2.86 +Ig2f=-j2.86 + + -- cgit