From b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b Mon Sep 17 00:00:00 2001 From: priyanka Date: Wed, 24 Jun 2015 15:03:17 +0530 Subject: initial commit / add all books --- 503/CH3/EX3.21/ch3_21.sci | 23 +++++++++++++++++++++++ 1 file changed, 23 insertions(+) create mode 100755 503/CH3/EX3.21/ch3_21.sci (limited to '503/CH3/EX3.21') diff --git a/503/CH3/EX3.21/ch3_21.sci b/503/CH3/EX3.21/ch3_21.sci new file mode 100755 index 000000000..252172e75 --- /dev/null +++ b/503/CH3/EX3.21/ch3_21.sci @@ -0,0 +1,23 @@ +// to calculate fault currentin feeder lines,primary and secondary lines of receiving end transformers + +clc; + +r=60; //kva rating of 3-ph common base +s=200; //kva rating of 3ph transformer +//sending end +X_Tse=.06*r/s; //.06= reactance of transformer based on its own rating +//in 2 kv feeder +V_B=2000/sqrt(3); //line to neutral +I_B=r*1000/(sqrt(3)*2000); +Z_B=V_B/I_B; +X_feeder=0.7/Z_B; //feeder reactance=0.7 +//receiving end +X_Tre=0.0051; +X_tot=X_Tse+X_feeder+X_Tre; +V_se=20/20; +I_fc=V_se/X_tot; //feeder current + +I_f=I_fc*I_B; disp(I_f,'current in 2kv feeder(A)'); +I_t1=I_f/sqrt(3); disp(I_t1,'current in 2kv winding of transformer(A)'); +I_t2=I_t1*10; disp(I_t2,'current in 200kv winding of transformer(A)'); +I_l=I_t2*sqrt(3); disp(I_l,'current at load terminals(A)'); \ No newline at end of file -- cgit