From 7f60ea012dd2524dae921a2a35adbf7ef21f2bb6 Mon Sep 17 00:00:00 2001 From: prashantsinalkar Date: Tue, 10 Oct 2017 12:27:19 +0530 Subject: initial commit / add all books --- 3872/CH12/EX12.3/Ex12_3.sce | 19 +++++++++++++++++++ 1 file changed, 19 insertions(+) create mode 100644 3872/CH12/EX12.3/Ex12_3.sce (limited to '3872/CH12/EX12.3/Ex12_3.sce') diff --git a/3872/CH12/EX12.3/Ex12_3.sce b/3872/CH12/EX12.3/Ex12_3.sce new file mode 100644 index 000000000..7b71197ab --- /dev/null +++ b/3872/CH12/EX12.3/Ex12_3.sce @@ -0,0 +1,19 @@ +//Book - Power System: Analysis & Design 5th Edition +//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye +//Chapter - 12 ; Example 12.3 +//Scilab Version - 6.0.0 ; OS - Windows + +clc; +clear; + +M=500; //MVA rating of the generator +f=60; //requency in Hertz +R=0.05; //Regulation constant in pu +delF=0.01; //Increase in frequency in Hertz + +delFpu=delF/f; //Frequency increase in pu +delPref=0; //Since fixed reference power setting is assumed +delPmpu=delPref-(1/R)*delFpu //Change in mechanical power in pu +delPm=delPmpu*M; //Actual value of mechanical power in MW + +printf('The turbine mechanical power output decreases by %.3f MW.',abs(delPm)) -- cgit