From 7f60ea012dd2524dae921a2a35adbf7ef21f2bb6 Mon Sep 17 00:00:00 2001 From: prashantsinalkar Date: Tue, 10 Oct 2017 12:27:19 +0530 Subject: initial commit / add all books --- 3872/CH10/EX10.9/EX10_9.sce | 20 ++++++++++++++++++++ 1 file changed, 20 insertions(+) create mode 100644 3872/CH10/EX10.9/EX10_9.sce (limited to '3872/CH10/EX10.9/EX10_9.sce') diff --git a/3872/CH10/EX10.9/EX10_9.sce b/3872/CH10/EX10.9/EX10_9.sce new file mode 100644 index 000000000..b5f8f1c92 --- /dev/null +++ b/3872/CH10/EX10.9/EX10_9.sce @@ -0,0 +1,20 @@ +//Book - Power System: Analysis & Design 5th Edition +//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye +//Chapter - 10 ; Example 10.9 +//Scilab Version - 6.0.0 ; OS - Windows + +clc; +clear; + +Srated = 10; //power rating in MVA +Vprtr = 80; //primary side of transformer voltage in kV +Vsectr = 20; //secondary side of transformer voltage in kV +CTratiopr = 150/5; //primary CT ratio +CTratiosec = 600/5; //secondary CT ratio +I1rated = (Srated*10^6)/(Vprtr*10^3); //rated current 1 in Amperes +I2rated = (Srated*10^6)/(Vsectr*10^3); //rated current 2 in Amperes +I1 = I1rated/CTratiopr; //differential current 1 in Amperes +I2 = I2rated/CTratiosec; //differential current 2 in Amperes +I = I1-I2; //differential current at rated conditions in Amperes +k = 0.5/2.25; //from figure 10.34 +printf('The value of k is %f',k); -- cgit