From b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b Mon Sep 17 00:00:00 2001 From: priyanka Date: Wed, 24 Jun 2015 15:03:17 +0530 Subject: initial commit / add all books --- 2015/CH7/EX7.16/7_16.sce | 40 ++++++++++++++++++++++++++++++++++++++++ 1 file changed, 40 insertions(+) create mode 100755 2015/CH7/EX7.16/7_16.sce (limited to '2015/CH7/EX7.16') diff --git a/2015/CH7/EX7.16/7_16.sce b/2015/CH7/EX7.16/7_16.sce new file mode 100755 index 000000000..0816e2f82 --- /dev/null +++ b/2015/CH7/EX7.16/7_16.sce @@ -0,0 +1,40 @@ + +clc +//initialisation of variables +clear +uw=2.5 +aw=127.82 +to=34 //temp in degrees +tr=26 //temp in degrees +ur=1.5 +ar=90 +ag=8.68 +clf1=100 +pvwo=0.037782 +p=1.013 //pressure in bar +a=6.66*10^-4 +phi=0.5 +//CALCULATIONS +shgw=uw*aw*(to-tr) +shgr=ur*ar*(to-tr) +sg=ag*clf1 +pvo=pvwo-(p*a*(to-tr)) +wo=0.622*(pvo/(p-pvo)) +ho=(1.005*to+wo*(2500+1.86*to)) +pvr=phi*pvo +wr1=0.622*(pvr/(p-pvr)) +hr=(1.005*tr+wr1*(2500+1.86*tr)) +//RESULTS +disp('recommended indoor conditions are25.5-26.7 degrees and 50% rh and outdoor conditions are 26 degrees and 50%rh') +disp('area of the roof is 90 m*m') +disp('overall heat transfer coefficients are2.5 w/m*m') +printf('\nsensible heat gain through walls is %2f',shgw) +printf('\nsensible heat gain through roofs is %2f',shgr) +printf('\nsensible heat gain through windows is %2f',sg) +disp('sensible heat per adult male is 67.5w and latent heat is 55.7w') +printf('\nenthalpy rate o is %2f',ho) +printf('\nenthalpy rate r is %2f',hr) +disp('volume of air infiltered is 1.628 m*m*m/min') +disp('latent heat gain is 902.4w') +disp('sensible heat gain is 257.2w') +disp('room sensible heat factor is 0.803') -- cgit