From b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b Mon Sep 17 00:00:00 2001 From: priyanka Date: Wed, 24 Jun 2015 15:03:17 +0530 Subject: initial commit / add all books --- 1445/CH7/EX7.34/Ex7_34.sce | 41 +++++++++++++++++++++++++++++++++++++++++ 1 file changed, 41 insertions(+) create mode 100644 1445/CH7/EX7.34/Ex7_34.sce (limited to '1445/CH7/EX7.34') diff --git a/1445/CH7/EX7.34/Ex7_34.sce b/1445/CH7/EX7.34/Ex7_34.sce new file mode 100644 index 000000000..eaf48effe --- /dev/null +++ b/1445/CH7/EX7.34/Ex7_34.sce @@ -0,0 +1,41 @@ +//CHAPTER 7- SINGLE PHASE TRANSFORMER +//Example 35 + +disp("CHAPTER 7"); +disp("EXAMPLE 35"); + +//single phase 50 hz, 200kVA, 11kVA/230 V +//open circuit and short circuit tests +//VARIABLE INITIALIZATION +va=200000; //apparent power +v1=11000; //primary voltage in Volts +v2=230; //secondary voltage in Volts +Woc=1600; //watts also equals core losses +Wc=2600; //watts, also equals cu losses +f=50; +//no load parameters +//day cycle given +h1=8; // hours +load1=160000; //load in watts +pf1=0.8; //power factor +h2=6; +load2=100000; +pf2=1; +h3=10; +load3=0; +pf3=0; +//SOLUTION +//24 hr energy output +Pout=load1*h1*pf1+load2*h2*pf2+load3*h3*pf3; +Pc24=Woc*24; // 24 hours Pc loss +//cu loss= hours.(kva output/kva rated)^2.Full load Cu loss +Pcu24=h1*(load1/va)^2*Wc+h2*(load2/va)^2*Wc+h3*(load3/va)^2*Wc; +Pin=Pout+Pc24+Pcu24; +eff=Pout*100/Pin; +//disp(sprintf("The value Pout is %f",Pout)); +//disp(sprintf("The value Pc is %f",Pc24)); +//disp(sprintf("The value Pcu is %f",Pcu24)); +disp(sprintf("The percent efficiency at full load is %.2f",eff)); +disp(" "); +// +//END -- cgit