+//Book - Power System: Analysis & Design 5th Edition
+//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye
+//Chapter - 10 ; Example 10.3
+//Scilab Version - 6.0.0 ; OS - Windows
+clc;
+clear;
+Crnttap=6; //Current tap setting in Amperes
+TDsetting=1; //Time dial setting
+CTratio=100/5; //CT ratio
+IZB=[5 0.5; 8 0.8; 15 1.5]; //Secondary output current in Amperes and burden resistance in Ohm
+RC_multiple_Crntap=IZB(1,1)/Crnttap; //Relay current in the multiple of the current tap setting
+printf('\nCase: a');
+if (RC_multiple_Crntap<1) then
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will not operate',RC_multiple_Crntap);
+else
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will operate after %0.2f Seconds',RC_multiple_Crntap,time);
+end
+RC_multiple_Crntap=IZB(2,1)/Crnttap; //Relay current in the multiple of the current tap setting
+time=6 //Relay operating time from figure 10.12 in Seconds
+printf('\n\nCase: b');
+if (RC_multiple_Crntap<1) then
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will not operate',RC_multiple_Crntap);
+else
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will operate after %d Seconds',RC_multiple_Crntap,time);
+end
+RC_multiple_Crntap=IZB(3,1)/Crnttap; //Relay current in the multiple of the current tap setting
+time=1.2 //Relay operating time from figure 10.12 in Seconds
+printf('\n\nCase: c');
+if (RC_multiple_Crntap<1) then
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will not operate',RC_multiple_Crntap);
+else
+ printf('\nFor the relay current in the multiple of the current tap setting %0.4f \nThe relay will operate after %0.2f Seconds',RC_multiple_Crntap,time);
+end