+clc;
+P=20000; // rated VA of transformer
+E1=3300; // rated voltage of primary
+E2=220; // rated voltage of secondary
+v2=220; // voltage at which load is getting delivered
+p=14960; // load power in Watts
+pf=0.8; // power factor at on load
+pc=160; // core loss
+pfo=0.15; // power factor at no load
+il=p/(v2*pf); // load current
+is=P/E2; // rated current of secondary
+vr=1 ; // percentage voltage drop of rated voltage in total resistance
+vx=3 ; // percentage voltage drop of rated voltage in total leakage reactance
+re2=(E2*vr)/(is*100); // total resistance referred to secondary
+xe2=(E2*vx)/(is*100); // total leakage reactance referred to secondary
+poh=il^2*re2; // ohmic losses
+pi=poh+pc+p; // total input power
+// E2 as a reference
+i2=il*(pf-%i*sqrt(1-pf^2));
+E2n=v2+i2*(re2+%i*xe2); // secondary winding voltage
+io=pc/(pfo*E2); // no load current
+ic=pc/E2; // core loss current
+im=sqrt(io^2-ic^2); // magnetizing current
+I=i2+(ic-im*%i); // total input current, negative sign before im indicates that it lags behind E2 by 90 degree
+pfi=cos(atan(imag(I),real(I))); // input power factor
+printf('Total input power is %f W \n',pi);
+printf('Input power factor is %f lagging',pfi);
+