+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART III : SWITCHGEAR AND PROTECTION
+// CHAPTER 1: SYMMETRICAL SHORT CIRCUIT CAPACITY CALCULATIONS
+
+// EXAMPLE : 1.6 :
+// Page number 471
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+kVA_gen = 21000.0 // Generator rating(kVA)
+kV_gen = 13.8 // Voltage rating of generator(kV)
+X_tr_gen = 30.0 // Transient reactance of generator(%)
+kVA_trans = 7000.0 // Transformer rating(kVA)
+kV_trans_lv = 13.8 // LV voltage rating of transformer(kV)
+kV_trans_hv = 66.0 // HV voltage rating of transformer(kV)
+X_trans = 8.4 // Reactance of transformer(%)
+l = 50.0 // Tie line length(miles)
+x = 0.848 // Reactance of tie line(ohm/mile)
+l_fault = 20.0 // Location of fault from station A(miles)
+
+// Calculations
+kVA_base = kVA_gen // Base rating(kVA)
+kV_base_lv = kV_trans_lv // Base voltage on L.V side(kV)
+kV_base_hv = kV_trans_hv // Base voltage on H.V side(kV)
+Z_gen_pu = %i*X_tr_gen/100 // Impedance of generator(p.u)
+Z_trans_pu = %i*X_trans*3/100 // Impedance of transformer(p.u)
+Z_F_left = %i*x*l_fault*kVA_base/(kV_base_hv**2*1000) // Impedance of line to left of fault F(p.u)
+Z_F_right = Z_F_left*(l-l_fault)/l_fault // Impedance of line to right of fault(p.u)
+Z_AF = Z_gen_pu+Z_trans_pu+Z_F_left // Impedance(p.u)
+Z_BF = Z_gen_pu+Z_trans_pu+Z_F_right // Impedance(p.u)
+Z_eq = Z_AF*Z_BF/(Z_AF+Z_BF) // Equivalent impedance(p.u)
+I_F = 1.0/abs(Z_eq) // Fault current(p.u)
+I_base = kVA_base/(3**0.5*kV_base_hv) // Base current(A)
+I_F_actual = I_F*I_base // Actual fault current(A)
+
+// Results
+disp("PART III - EXAMPLE : 1.6 : SOLUTION :-")
+printf("\nActual fault current = %.f A \n", I_F_actual)
+printf("\nNOTE: Changes in the obtained answer from that of textbook is due to more precision here")