{ "cells": [ { "cell_type": "markdown", "metadata": {}, "source": [ "# Chapter 7 : Air Conditioning" ] }, { "cell_type": "markdown", "metadata": {}, "source": [ "## Example 7.1 Page no : 345" ] }, { "cell_type": "code", "execution_count": 1, "metadata": { "collapsed": false }, "outputs": [ { "name": "stdout", "output_type": "stream", "text": [ "Heating capacity of coil is 5.40 kW \n", "Surface temperature of coil is 35 C \n", "Capacity of humidifier is 3.33 kg/hr\n" ] } ], "source": [ "\n", "# Variables\n", "DBTo = 10.;\t\t\t#Out door Dry bulb temperature in oC\n", "WBTo = 8.;\t\t\t#Out door Wet bulb temperature in oC\n", "DBTi = 20.;\t\t\t#In door Dry bulb temperature in oC\n", "RH = 0.6;\t\t\t#Re-Heat factor\n", "a = 0.3;\t\t\t#amount of air circulated in (m**3)/min/person\n", "S = 50.;\t\t\t#Seating capacity of office\n", "BPF = 0.32;\t\t\t#ByPass factor\n", "ha = 25.;\t\t\t#Enthalpy at point a from Psychrometric chart shown in Page 346 in kJ/kg\n", "hb = 42.5;\t\t\t#Enthalpy at point b from Psychrometric chart shown in Page 346 in kJ/kg\n", "hc = 42.5;\t\t\t#Enthalpy at point c from Psychrometric chart shown in Page 346 in kJ/kg\n", "Wa = 0.006;\t\t\t#Specific humidity at point a from Psychrometric chart shown in Page 346 in kg/kg dry air\n", "Wc = 0.009;\t\t\t#Specific humidity at point c from Psychrometric chart shown in Page 346 in kg/kg dry air\n", "Tb = 27.;\t\t\t#Temperature at point b in oC\n", "na = 0.81;\t\t\t#Specific Volume from Psychrometric chart shown in page 346 in (m**3)/kg\n", "\n", "# Calculations\n", "ma = (a*S)/(na*60);\t\t\t#mass of air circulated per second in kg/s\n", "Hc = ma*(hb-ha);\t\t\t#Heating capacity of coil in kW\n", "Ts = (Tb-(BPF*DBTo))/(1-BPF);\t\t\t#Heating coil surface temperature in oC\n", "C = (ma*3600)*(Wc-Wa);\t\t\t#Capacity of humidifier in kg/hr\n", "\n", "# Results\n", "print 'Heating capacity of coil is %3.2f kW \\\n", "\\nSurface temperature of coil is %3.0f C \\\n", "\\nCapacity of humidifier is %3.2f kg/hr'%(Hc,Ts,C)\n", "\n", "# rounding off error" ] }, { "cell_type": "markdown", "metadata": {}, "source": [ "## Example 7.2 Page no : 346" ] }, { "cell_type": "code", "execution_count": 2, "metadata": { "collapsed": false }, "outputs": [ { "name": "stdout", "output_type": "stream", "text": [ "Capacity of cooling coil is 6.16 tonnes \n", "Capacity of heating coil is 3.6 kW \n", "Amount of water vapour removed per hour is 17.80 kg/hr \n", "Bypass factor is 0.385\n" ] } ], "source": [ "# Variables\n", "S = 60.;\t\t\t#No. of staff\n", "DBTo = 30.;\t\t\t#Out door Dry bulb temperature in oC\n", "RHo = 0.7;\t\t\t#Re-Heat factor at out-door\n", "a = 0.4;\t\t\t#amount of air circulated in (m**3)/min/person\n", "DBTi = 20.;\t\t\t#In door Dry bulb temperature in oC\n", "RHi = 0.6;\t\t\t#Re-Heat factor at indoor\n", "Td = 25.;\t\t\t#Heating coil surface temperature in oC\n", "ha = 82.5;\t\t\t#Enthalpy at point a from Psychrometric chart shown in Page 347 in kJ/kg\n", "hb = 34.5;\t\t\t#Enthalpy at point b from Psychrometric chart shown in Page 347 in kJ/kg\n", "hc = 42.5;\t\t\t#Enthalpy at point c from Psychrometric chart shown in Page 347 in kJ/kg\n", "Wa = 0.020;\t\t\t#Specific humidity at point a from Psychrometric chart shown in Page 347 in kg/kg dry air\n", "Wb = 0.009;\t\t\t#Specific humidity at point b from Psychrometric chart shown in Page 347 in kg/kg dry air\n", "Tb = 12.;\t\t\t#Temperature at point b in oC\n", "na = 0.89;\t\t\t#Specific Volume from Psychrometric chart shown in page 346 in (m**3)/kg\n", "\n", "# Calculations\n", "ma = (a*S)/(na*60);\t\t\t#mass of air circulated per second in kg/s\n", "Hc = (ma*(ha-hb))/3.5;\t\t\t#Heating capacity of cooling coil in tonnes\n", "Hh = ma*(hc-hb);\t\t\t#Heating capacity of heating coil in kW\n", "W = (ma*3600)*(Wa-Wb);\t\t\t#Amount of water vapour removed per hour in kg/hr\n", "BPF = (Td-DBTi)/(Td-Tb);\t\t\t#By-Pass factor\n", "\n", "# Results\n", "print 'Capacity of cooling coil is %3.2f tonnes \\\n", "\\nCapacity of heating coil is %3.1f kW \\\n", "\\nAmount of water vapour removed per hour is %3.2f kg/hr \\\n", "\\nBypass factor is %3.3f'%(Hc,Hh,W,BPF)\n" ] }, { "cell_type": "markdown", "metadata": {}, "source": [ "## Example 7.3 Page no : 347" ] }, { "cell_type": "code", "execution_count": 2, "metadata": { "collapsed": false }, "outputs": [ { "name": "stdout", "output_type": "stream", "text": [ "Supply air condition to the room is 2.74 kg/s \n", "Refrigeration load due to reheat is 4.93 ton \n", "Total refrigerating capacity is 16.28 ton \n", "Quantity of fresh air supplied is 0.365 m**3/s\n" ] } ], "source": [ "\n", "\n", "# Variables\n", "RSH = 10.;\t\t\t#Room sensible heat in kW\n", "RLH = 10.;\t\t\t#Room latent heat in kW\n", "td1 = 25.;\t\t\t#Inside temperature in oC\n", "RH1 = 0.5;\t\t\t#Inside Re-Heat factor\n", "h1 = 50.4;\t\t\t#Enthalpy at point 1 in kJ/kg\n", "td2 = 35.;\t\t\t#Out door Dry bulb temperature in oC\n", "tw2 = 28.;\t\t\t#Out door Wet bulb temperature in oC\n", "CR = 4.;\t\t\t#Cooling coil ratio\n", "BPF = 0.1;\t\t\t#Cooling coil bypass factor\n", "tADP = 10;\t\t\t#Apparatus dew point temperature in oC\n", "RH3 = 0.55;\t\t\t#Re-Heat factor at point 3\n", "h3 = 58.2;\t\t\t#Enthalpy at point 3 in kJ/kg\n", "RH4 = 0.95;\t\t\t#Re-Heat factor at point 4\n", "h4 = 32.2;\t\t\t#Enthalpy at point 4 in kJ/kg\n", "RH5 = 0.81;\t\t\t#Re-Heat factor at point 5\n", "h5 = 36.8;\t\t\t#Enthalpy at point 5 in kJ/kg\n", "RH6 = 0.54;\t\t\t#Re-Heat factor at point 6\n", "h6 = 43.1;\t\t\t#Enthalpy at point 5 in kJ/kg\n", "td6 = 22.;\t\t\t#Temperature at point 6 in oC\n", "\n", "# Calculations\n", "td3 = ((td2-td1)/5)+td1;\t\t\t#Temperature at point 3 from Psychrometric chart shown in Page 348 in oC\n", "td4 = (BPF*(td3-tADP))+tADP;\t\t\t#Temperature at point 4 from Psychrometric chart shown in Page 348 in oC\n", "td5 = td4+((td1-td4)/5);\t\t\t#Temperature at point 5 from Psychrometric chart shown in Page 348 in oC\n", "RSHF = RSH/(RSH+RLH);\t\t\t#Room Sensible Heat Factor\n", "QR = h1-h6;\t\t\t#Total heat removed in kJ/kg\n", "S = (RSH+RLH)/QR;\t\t\t#Supply air quantity in kg/s\n", "R = (S*(h6-h5))/3.5;\t\t\t#Refrigeration load due to reheat in ton\n", "D = (S*4)/5;\t\t\t#Dehumidified air quantity in kg/s\n", "T = (D*(h3-h4))/3.5;\t\t\t#Total refrigerating capacity in ton\n", "Q = (D/5)/1.2;\t\t\t#Quantity of fresh air supplied in (m**3)/s\n", "\n", "# Results\n", "print 'Supply air condition to the room is %3.2f kg/s \\\n", "\\nRefrigeration load due to reheat is %3.2f ton \\\n", "\\nTotal refrigerating capacity is %3.2f ton \\\n", "\\nQuantity of fresh air supplied is %3.3f m**3/s'%(S,R,T,Q)\n" ] } ], "metadata": { "kernelspec": { "display_name": "Python 2", "language": "python", "name": "python2" }, "language_info": { "codemirror_mode": { "name": "ipython", "version": 2 }, "file_extension": ".py", "mimetype": "text/x-python", "name": "python", "nbconvert_exporter": "python", "pygments_lexer": "ipython2", "version": "2.7.6" } }, "nbformat": 4, "nbformat_minor": 0 }